Greenhouse Lab Relative Humidity Meter Digital Thermohygrometer Hygrometer
Feature:
1. ABS shell and LCD largescreen clearly display data;
2. RS485 signal output can monitor temperature and humidity in real time for a long time on line;
3. Built in probe, moisture-proof and dust-proof, small and generous, integrated installation, convenient operation;
4. Mainly used in warehouses, machine rooms, offices, pharmacies, laboratorie.
Attention:
1. The horizontal distance from the sensor to the air supply outlet of the air conditioner shall be greater than 1.5m, and the distance to the ceiling air supply outlet shall be greater than 0.5m.
2. In order to prevent the cold air under the isolated floor from affecting the true test of the sensor through the trunking, PVC terminals should be added at the upper port of the trunking, or the sensor should be installed at the side of the trunking.
Voltage |
12V DC (Range: 6~15V DC) |
||
Max power |
≤1.2W |
||
Accuracy |
Humidity |
≤±2%RH (60% 25℃) |
|
Temperature |
≤±0.3℃ (25℃) |
||
Range |
Humidity |
0~100%RH |
|
Temperature |
-20℃ ~ +70℃ |
||
Working environment of transmitter circuit |
Humidity |
0%RH~80%RH |
|
Temperature |
-20℃ ~ +60℃ |
||
Working temperature of probe |
Built in probe |
-40℃ ~ +100℃ |
|
Epitaxial hardbound probe |
|||
Extended waterproof probe |
|||
Working humidity of probe |
0~100%RH |
||
Effective working area |
10~20 m2/unit |
||
Output signal |
RS485 output MODBUS-RTU (4-20mA can be customized) |
||
Installation method |
Indoor wall installation or ceiling installation. |
||
Resolution |
Temperature |
0.1℃ (25℃) |
|
Humidity |
0.1%RH (60% 25℃) |
||
Response time |
1S |
||
Long term stability |
Temperature |
≤0.1℃/y |
|
Humidity |
≤1%RH/y |
Contact: Boboscot.xie
Phone: +8613802394840
Tel: 0769-81052116
Email: yuluo@dax-instruments.com